Power factor calculation:
PF = |cos φ| = 1000 × P(kW) / (V(V) × I(A))
Apparent power calculation:
|S(kVA)| = V(V) × I(A) / 1000
Reactive power calculation:
Q(kVAR) = √(|S(kVA)|2 - P(kW)2)
Power factor correction capacitor's capacitance calculation:
Scorrected (kVA) = P(kW) / PFcorrected
Qcorrected (kVAR) = √(Scorrected (kVA)2 - P(kW)2)
Qc (kVAR) = Q(kVAR) - Qcorrected (kVAR)
C(F) = 1000 × Qc (kVAR) / (2πf(Hz)×V(V)2)
For three phase with balanced loads:
Power factor calculation:
PF = |cos φ| = 1000 × P(kW) / (√3 × VL-L(V) × I(A))
Apparent power calculation:
|S(kVA)| = √3 × VL-L(V) × I(A) / 1000
Reactive power calculation: